A Differential Voltage-Based Wide-Area Backup Protection Scheme for Transmission Network

This article proposes a differential voltage-based scheme to identify the faulted line in the transmission system. Initially, the placement of phasor measurement unit (PMU) is carried out. Based on the PMU placement, three subnetwork types are evaluated. Further, a differential voltage-based algorit...

Celý popis

Uložené v:
Podrobná bibliografia
Vydané v:IEEE systems journal Ročník 16; číslo 1; s. 520 - 530
Hlavní autori: Shalini, Samantaray, Subhransu Ranjan
Médium: Journal Article
Jazyk:English
Vydavateľské údaje: New York IEEE 01.03.2022
The Institute of Electrical and Electronics Engineers, Inc. (IEEE)
Predmet:
ISSN:1932-8184, 1937-9234
On-line prístup:Získať plný text
Tagy: Pridať tag
Žiadne tagy, Buďte prvý, kto otaguje tento záznam!
Popis
Shrnutí:This article proposes a differential voltage-based scheme to identify the faulted line in the transmission system. Initially, the placement of phasor measurement unit (PMU) is carried out. Based on the PMU placement, three subnetwork types are evaluated. Further, a differential voltage-based algorithm is applied to each subnetwork in a system. The tripping decisions for each dependent subnetwork are carried out in steps by providing separate timer settings for them. The load encroachment and fault conditions for a particular case is distinguished by applying modified distance relaying and sequence component-based algorithms to the proposed differential voltage-based scheme. Extensive tests are carried out for several fault and stressed conditions on a New England 39-bus system on MATLAB/Simulink platform. The proposed scheme is also validated for different test cases on a modified WSCC 9-bus system on real-time digital simulator platform for assessing its ability to perform in real time.
Bibliografia:ObjectType-Article-1
SourceType-Scholarly Journals-1
ObjectType-Feature-2