Duty-cycling buildings aggressively: The next frontier in HVAC control

Buildings are known to be the largest consumers of electricity in the United States, and often times the dominant energy consumer is the HVAC system. Despite this fact, in most buildings the HVAC system is run using primitive static control algorithms based on fixed work schedules causing wasted ene...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:2011 10th International Conference on Information Processing in Sensor Networks S. 246 - 257
Hauptverfasser: Agarwal, Yuvraj, Balaji, Bharathan, Dutta, Seemanta, Gupta, Rajesh K, Weng, Thomas
Format: Tagungsbericht
Sprache:Englisch
Veröffentlicht: IEEE 01.04.2011
Schlagworte:
ISBN:9781612848549, 1612848540
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Buildings are known to be the largest consumers of electricity in the United States, and often times the dominant energy consumer is the HVAC system. Despite this fact, in most buildings the HVAC system is run using primitive static control algorithms based on fixed work schedules causing wasted energy during periods of low occupancy. In this paper we present a novel control architecture that uses occupancy sensing to guide the operation of a building HVAC system. We show how we can enable aggressive duty-cycling of building HVAC systems - that is, turn them ON or OFF - to save energy while meeting building performance requirements using inexpensive sensing and control methods. We have deployed our occupancy sensor network across an entire floor of a university building and our data shows several periods of low occupancy with significant opportunities to save energy over normal HVAC schedules. Furthermore, by interfacing with the building Energy Management System (EMS) directly and using real-time occupancy data collected by our occupancy nodes, we measure electrical energy savings of 9.54% to 15.73% and thermal energy savings of 7.59% to 12.85% for the HVAC system by controlling just one floor of our four floor building.
ISBN:9781612848549
1612848540