A System Analysis of Cold Storage using the New Non-Freon Refrigerant GF-08
The equipment for chilling or freezing food consumes much energy. Therefore, there is a need to reduce the energy consumption. Also, to contribute to reduce the greenhouse gas (GHG) emissions, it is necessary to replace conventional refrigerants which affect Global Warming because of high Global War...
Uložené v:
| Vydané v: | Chemical Engineering Transactions Ročník 78 |
|---|---|
| Hlavní autori: | , |
| Médium: | Journal Article |
| Jazyk: | English |
| Vydavateľské údaje: |
AIDIC Servizi S.r.l
01.02.2020
|
| Predmet: | |
| ISSN: | 2283-9216, 2283-9216 |
| On-line prístup: | Získať plný text |
| Tagy: |
Pridať tag
Žiadne tagy, Buďte prvý, kto otaguje tento záznam!
|
| Abstract | The equipment for chilling or freezing food consumes much energy. Therefore, there is a need to reduce the energy consumption. Also, to contribute to reduce the greenhouse gas (GHG) emissions, it is necessary to replace conventional refrigerants which affect Global Warming because of high Global Warming Potential (GWP). Hence, there is a need for the use of alternative refrigerants with lower GWPs. Therefore, in this study, the potential of the non-freon refrigerant GF-08, which consists of hydro-carbons, as an alternative refrigerant was evaluated. The use of GF-08 for chilling and freezing storage systems was evaluated. The eco-benefits of GF-08 in comparison to the conventional refrigerant (R404A) was evaluated by developing a theoretical simulation model. A demo-test using a refrigerator in a restaurant was conducted to validate the simulated result. This result showed that performance differences depend on different operating conditions of temperature. Based on the simulation model, the benefits considering the energy reduction was evaluated. The reduction of the annual energy consumption, and the environmental impact of GF-08 using the life cycle assessment (LCA) methodology were estimated. The use of GF-08 reduced the annual energy consumption by 28.6% and the GHG emissions by 27.1 % in comparison to the R404A. |
|---|---|
| AbstractList | The equipment for chilling or freezing food consumes much energy. Therefore, there is a need to reduce the energy consumption. Also, to contribute to reduce the greenhouse gas (GHG) emissions, it is necessary to replace conventional refrigerants which affect Global Warming because of high Global Warming Potential (GWP). Hence, there is a need for the use of alternative refrigerants with lower GWPs. Therefore, in this study, the potential of the non-freon refrigerant GF-08, which consists of hydro-carbons, as an alternative refrigerant was evaluated. The use of GF-08 for chilling and freezing storage systems was evaluated. The eco-benefits of GF-08 in comparison to the conventional refrigerant (R404A) was evaluated by developing a theoretical simulation model. A demo-test using a refrigerator in a restaurant was conducted to validate the simulated result. This result showed that performance differences depend on different operating conditions of temperature. Based on the simulation model, the benefits considering the energy reduction was evaluated. The reduction of the annual energy consumption, and the environmental impact of GF-08 using the life cycle assessment (LCA) methodology were estimated. The use of GF-08 reduced the annual energy consumption by 28.6% and the GHG emissions by 27.1 % in comparison to the R404A. |
| Author | Kiyoshi Dowaki Shun Kataniwa |
| Author_xml | – sequence: 1 fullname: Shun Kataniwa – sequence: 2 fullname: Kiyoshi Dowaki |
| BackLink | https://cir.nii.ac.jp/crid/1874242817344376064$$DView record in CiNii |
| BookMark | eNpNjLFOwzAURS1UJErpwhd4YA3Yzy-2M1YVLYiqSBTmyHHs4Kq1kROE-vcUysBw7z26w7kko5iiI-Sas1shmLizbgCmNBNwRsYAWhQVcDn6xxdk2vdbxhhwzTXKMXma0c2hH9yezqLZHfrQ0-TpPO1auhlSNp2jn32IHR3eHV27L7pOsVhklyJ9cT6HzmUTB7pcFExfkXNvdr2b_u2EvC3uX-cPxep5-TifrYoWBB8KI4EZsIp745TlwvKmBMlbaTW0rWl4ya0pwTqUJXjgiCUKL22pGnRYWTEhjydvm8y2_shhb_KhTibUv0fKXW3yEOzO1UxLXzW2Mo1meEzlsTTMKcUrrzSqo-vm5Ioh1Db8NNcKAUFzJRCFkkyi-AYEgmWP |
| ContentType | Journal Article |
| DBID | RYH DOA |
| DOI | 10.3303/cet2078032 |
| DatabaseName | CiNii Complete DOAJ Directory of Open Access Journals |
| DatabaseTitleList | |
| Database_xml | – sequence: 1 dbid: DOA name: DOAJ Directory of Open Access Journals url: https://www.doaj.org/ sourceTypes: Open Website |
| DeliveryMethod | fulltext_linktorsrc |
| EISSN | 2283-9216 |
| ExternalDocumentID | oai_doaj_org_article_086f9bc9ab804b809f45a0e7719f7847 |
| GroupedDBID | ACCJX ALMA_UNASSIGNED_HOLDINGS GROUPED_DOAJ OK1 RYH |
| ID | FETCH-LOGICAL-d231t-a620a2c71fae7c13c1b5261d6c82ddab151ca52ce4652f2144543f6c57b4e49c3 |
| IEDL.DBID | DOA |
| ISSN | 2283-9216 |
| IngestDate | Fri Oct 03 12:41:17 EDT 2025 Thu Jun 26 21:53:54 EDT 2025 |
| IsDoiOpenAccess | true |
| IsOpenAccess | true |
| IsPeerReviewed | true |
| IsScholarly | true |
| Language | English |
| LinkModel | DirectLink |
| MergedId | FETCHMERGED-LOGICAL-d231t-a620a2c71fae7c13c1b5261d6c82ddab151ca52ce4652f2144543f6c57b4e49c3 |
| OpenAccessLink | https://doaj.org/article/086f9bc9ab804b809f45a0e7719f7847 |
| ParticipantIDs | doaj_primary_oai_doaj_org_article_086f9bc9ab804b809f45a0e7719f7847 nii_cinii_1874242817344376064 |
| PublicationCentury | 2000 |
| PublicationDate | 2020-02-01 |
| PublicationDateYYYYMMDD | 2020-02-01 |
| PublicationDate_xml | – month: 02 year: 2020 text: 2020-02-01 day: 01 |
| PublicationDecade | 2020 |
| PublicationTitle | Chemical Engineering Transactions |
| PublicationYear | 2020 |
| Publisher | AIDIC Servizi S.r.l |
| Publisher_xml | – name: AIDIC Servizi S.r.l |
| SSID | ssj0002181846 |
| Score | 2.149514 |
| Snippet | The equipment for chilling or freezing food consumes much energy. Therefore, there is a need to reduce the energy consumption. Also, to contribute to reduce... |
| SourceID | doaj nii |
| SourceType | Open Website Publisher |
| SubjectTerms | Chemical engineering Computer engineering. Computer hardware TK7885-7895 TP155-156 |
| Title | A System Analysis of Cold Storage using the New Non-Freon Refrigerant GF-08 |
| URI | https://cir.nii.ac.jp/crid/1874242817344376064 https://doaj.org/article/086f9bc9ab804b809f45a0e7719f7847 |
| Volume | 78 |
| hasFullText | 1 |
| inHoldings | 1 |
| isFullTextHit | |
| isPrint | |
| journalDatabaseRights | – providerCode: PRVAON databaseName: DOAJ Directory of Open Access Journals customDbUrl: eissn: 2283-9216 dateEnd: 99991231 omitProxy: false ssIdentifier: ssj0002181846 issn: 2283-9216 databaseCode: DOA dateStart: 20090101 isFulltext: true titleUrlDefault: https://www.doaj.org/ providerName: Directory of Open Access Journals |
| link | http://cvtisr.summon.serialssolutions.com/2.0.0/link/0/eLvHCXMwrV3BSsQwEA2yePAiioqrruTgNWybJk17XJetglBEV9hbSSeJ9NLKWv1-Z9oV9ubFQwttDqGvZN57MLxh7E4p8MolUuByECqGSFhtjAAfQooOmjoxhmETpiyzzSZ_3hv1RT1hYzzwCNwcJXfIa8htnUUKrzwobSNvTJwHg6WVqi-qnj0zRTWYiAuZdcwjRcuezJertUQ6jGjOyJDOj2TSNs0emRQn7HinAvli3P2UHfj2jD0t-Jgfzn-TQngXODp7x1_RGePB59Sl_s5Rs3EsTrzsWlFsfdfyFx_QZXvknZ4_FCLKztlbsVovH8Vu1oFwqLB6YVMZWQkmDtYbiBOIa43mxqWQSedsjcQMVksENtUyUM6ZVklIQZtaeZVDcsEmbdf6S8a1V5nToBOjAMUOpcfYKOSZrX1w-DRl9_T91ccYZ1FRwPTwAmGvdrBXf8E-ZTNEr4KG7jTXD6k-i02iFHXZpOrqPza5ZkeS7O3QJH3DJv32y8_YIXz3zef2dvjjP1xAq9k |
| linkProvider | Directory of Open Access Journals |
| openUrl | ctx_ver=Z39.88-2004&ctx_enc=info%3Aofi%2Fenc%3AUTF-8&rfr_id=info%3Asid%2Fsummon.serialssolutions.com&rft_val_fmt=info%3Aofi%2Ffmt%3Akev%3Amtx%3Ajournal&rft.genre=article&rft.atitle=A+System+Analysis+of+Cold+Storage+using+the+New+Non-Freon+Refrigerant+GF-08&rft.jtitle=Chemical+Engineering+Transactions&rft.au=Shun+Kataniwa&rft.au=Kiyoshi+Dowaki&rft.date=2020-02-01&rft.pub=AIDIC+Servizi+S.r.l&rft.issn=2283-9216&rft.eissn=2283-9216&rft_id=info:doi/10.3303%2Fcet2078032 |
| thumbnail_l | http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/lc.gif&issn=2283-9216&client=summon |
| thumbnail_m | http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/mc.gif&issn=2283-9216&client=summon |
| thumbnail_s | http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/sc.gif&issn=2283-9216&client=summon |