Probabilistic Under Frequency Load Shedding Considering RoCoF Relays of Distributed Generators

The activation of under frequency load shedding (UFLS) is the last automated action against the severe frequency drops in order to rebalance the system. In this paper, the setting parameters of a multistage load shedding plan are obtained and optimized using a discretized model of dynamic system fre...

Celý popis

Uložené v:
Podrobná bibliografia
Vydané v:IEEE transactions on power systems Ročník 33; číslo 4; s. 3587 - 3598
Hlavní autori: Amraee, Turaj, Darebaghi, Mohammad Ghaderi, Soroudi, Alireza, Keane, Andrew
Médium: Journal Article
Jazyk:English
Vydavateľské údaje: IEEE 01.07.2018
Predmet:
ISSN:0885-8950, 1558-0679
On-line prístup:Získať plný text
Tagy: Pridať tag
Žiadne tagy, Buďte prvý, kto otaguje tento záznam!
Popis
Shrnutí:The activation of under frequency load shedding (UFLS) is the last automated action against the severe frequency drops in order to rebalance the system. In this paper, the setting parameters of a multistage load shedding plan are obtained and optimized using a discretized model of dynamic system frequency response. The uncertainties of system parameters including inertia time constant, load damping, and generation deficiency are taken into account. The proposed UFLS model is formulated as a mixed-integer linear programming optimization problem to minimize the expected amount of load shedding. The activation of rate-of-change-of-frequency relays as the anti-islanding protection of distributed generators is considered. The Monte Carlo simulation method is utilized for modeling the uncertainties of system parameters. The results of probabilistic UFLS are then utilized to design four different UFLS strategies. The proposed dynamic UFLS plans are simulated over the IEEE 39-bus and the large-scale practical Iranian national grid.
ISSN:0885-8950
1558-0679
DOI:10.1109/TPWRS.2017.2787861